| Model Name/Number | PE HVTD 12/100 |
| Accuracy Tan Delta | +/- 1% of the reading |
| Cables With Carrying Case | Soft Carry case |
| Ranges Tan Delta | 0 to 1000 % in three ranges ( 0.1 , 1 & 10 ) |
| Resolution Tan Delta | 1 x 10 (-2) |
| Voltage Indication | 3 1/2 Digital Panel Meter (DPM) |
POWER ELECTRONICAL’s Manual Capacitance and Tan-Delta Test System (Model HVTD-12/100) has inbuilt HV Power Source, Standard Capacitor (SF6 Gas Filled), and set of cables.
The compact design of the system uses the principle of three winding differential transformer on a high permeability mu-metal core to measure the Capacitance of the object and its Tan-Delta value accurately.
The Capacitance & Dissipation Factor (Tan-Delta) Test System is contained in a sturdy metallic housing with mu-metal lining which shields it from external electromagnetic & electrostatic influences. Built-in battery powered Null indicator makes the system suitable for operation in workshop, factories, High Voltage Switch Yards etc.
It is suitable for both grounded as well as ungrounded objects. The system is provided with High Voltage Protection Devices which protect the system and operator against failure of test object or standard capacitor.
FEATURES:
- 12kV 100mA - Tan-Delta accuracy of 1 X 10 -4
- Low Dissipation factor Reference Standard Capacitor of 1 X 10E-5
- UST, GST and GSTg testing modes
- Open Ground Indication
- HT Cut- off on overload.
- All operating controls are at earth potential
APPLICATION
- Transformer testing
- Testing Bushings, CTs, PTs, etc at substations
- Testing Rotating machines (LV Motors/Generators) on-site